Zigzag-Delta-Wye Transformer
Linear, non-ideal zigzag-delta-wye transformer with three-limb core with saturation capability
Libraries:
Simscape /
Electrical /
Passive /
Transformers
Description
The Zigzag-Delta-Wye Transformer block models a linear, nonideal transformer with a three-limb core that has primary zigzag windings and secondary delta, wye, or delta and wye windings. You can specify the phase offset between the zigzag and wye windings using the Wye secondary phase shift parameter and parameterize the block impedance using per-unit values. The block includes effects for linear winding leakage and linear core magnetization.
The configuration options for the delta winding types are:
Delta 1 o'clock — Mesh configuration with a lagging 30-degree phase shift relative to the voltage of a connected wye configuration
Delta 11 o'clock — Mesh configuration with leading 30-degree phase shift relative to the voltage of a connected wye configuration
These equivalent circuit diagrams show the zigzag-delta-wye transformer in the delta 1 o'clock and delta 11 o'clock configurations, respectively.
In these diagrams:
Rw1 is the primary winding resistance.
Ll1 is the primary leakage reactance.
Rw2 is the delta secondary winding resistance.
Ll2 is the delta secondary leakage reactance.
Rw3 is the wye secondary winding resistance.
Ll3 is the wye secondary leakage reactance.
Rm is the shunt magnetizing resistance.
Lm is the shunt magnetizing reactance.
Variables
Use the Variables settings to specify the priority and initial target values for the block variables before simulation. For more information, see Set Priority and Initial Target for Block Variables.
To enable the Wye secondary currents variable, set
Secondary connection to Wye
or
Wye and Delta
.
To enable the Delta secondary currents variable, set
Secondary connection to Delta
or
Wye and Delta
.
Ports
Conserving
Parameters
Extended Capabilities
Version History
Introduced in R2019b